| Symptom |
Possible Cause |
Remedy |
| Unit will not run |
Power off or loose electrical
connection |
Check for correct voltage
at contactor in condensing unit |
| Thermostat out of calibration-set
too high |
Reset |
| Defective contactor |
Check for 24 volts at
contactor coil - replace if contacts are open |
| Blown fuses |
Replace fuses |
| Transformer defective |
Check wiring-replace
transformer |
| High pressure control
open (if provided) |
Reset-also see high
head pressure remedy - the high pressure control opens at 450
PSIG |
| Outdoor fan runs, compressor doesn't |
Run or start capacitor
defective |
Replace |
| Start relay defective |
Replace |
| Loose connection |
Check for correct voltage
at compressor - check & tighten all connections |
| Compressor stuck, grounded or open
motor winding, open internal overload. |
Wait at least 2 hours for overload
to reset. If still open, replace the compressor |
| Low voltage condition |
Add start kit components |
| Insufficient cooling |
Improperly sized unit |
Recalculate load |
| Improper indoor airflow |
Check - should be approximately
400 CFM per ton |
| Incorrect refrigerant charge |
Charge per procedure attached to
unit service panel |
| Air, non-condensibles or moisture
in system |
Recover refrigerant, evacuate &
recharge, add filter drier |
| Compressor short cycles |
Incorrect voltage |
At compressor terminals, voltage
must be ± 10 % of nameplate marking when unit is operating. |
| Defective overload protector |
Replace - check for correct voltage |
| Refrigerant undercharge |
Add refrigerant |
| Registers sweat |
Low indoor airflow |
Increase speed of blower or reduce
restriction - replace air filter |
| High head-low vapor pressures |
Restriction in liquid line, expansion
device or filter drier |
Remove or replace defective component |
| Flow check piston size too small |
Change to correct size piston |
| Incorrect capillary tubes |
Change coil assembly |
| High head-high or normal vapor pressure
- cooling mode |
Dirty outdoor coil |
Clean coil |
| Refrigerant overcharge |
Correct system charge |
| Outdoor fan not running |
Repair or replace |
| Air or non-condensibles in system |
Recover refrigerant, evacuate &
recharge |
| Low head-high vapor pressures |
Flow check piston size too large |
Change to correct size piston |
| Defective compressor valves |
Replace compressor |
| Incorrect capillary tubes |
Replace coil assembly |
| Low vapor - cool compressor - iced
indoor coil |
Low indoor airflow |
Increase speed of blower or reduce
restriction - replace air filter |
| Operating below 65°F outdoors |
Add low ambient kit |
| Moisture in system |
Recover refrigerant - evacuate &
recharge - add filter drier |
| High vapor pressure |
Excessive load |
Recheck load calculation |
| Defective compressor |
Replace |
| Fluctuating head & vapor pressures |
TXV hunting |
Check TXV bulb clamp - check air
distribution on coil - replace TXV |
| Air or non-condensibles in system |
Recover refrigerant, evacuate &
recharge |
| Gurgle or pulsing noise at expansion
device or liquid line |
Air or non-condensibles in system |
Recover refrigerant, evacuate &
recharge |
If you don't know which firm to call, ask if the contractor
is a member of the Air Conditioning Contractors of America (ACCA).
consumers can call (972)247-5383 or 1-800-260-8041 to confirm
the contractor is a member or to locate a contractor who subscribes
to the organization's code or ethics.